Technical Specifications |
4000 |
5000 |
MX Frame 15 000 |
MX Frame 20 000 |
Rating (kVA/kW) |
4 kVA / 3.6 kW |
5 kVA / 4.5 kW |
15 kVA / 13.5 kW |
20 kVA / 18 kW |
Paralleling |
Maximum rating / redundancy1 |
8 kVA / 4 kVA + 4 kVA redundancy |
10 kVA / 5 kVA + 5 kVA redundancy |
15 kVA / 10 kVA + 5 kVA redundancy |
20 kVA / 15 kVA + 5 kVA redundancy |
Inputs |
Technology |
VFI-SS-113, on-line double conversion with power factor correction, convection cooled static bypass switch |
Number of phases, input connections |
L + N, terminals up to 6 mm2 |
L + N, terminals up to 6 mm2 |
L + N or 3P + N, terminals up to 35 mm2, separate or common AC normal and AC bypass |
Nominal voltage |
200/208/220/230/240/250 V |
200/208/220/230/240/250 V |
200/208/220/230/240/250 V (L + N) or 380/400/415 V (3P + N) |
Voltage range without using battery2 |
120 - 280 V |
120 - 280 V |
120 - 280 V (L + N), 250 - 465 V (3P + N) |
Input frequency range, THDI |
40-70 Hz, < 7% |
Outputs |
Output connections3 |
Terminals + 8 IEC C13 (10A) + 2 IEC C19 (16A) |
Terminals + 8 IEC C13 (10A) + 4 IEC C19 (16A) |
Remotely controlled Powershare sockets |
2 groups (2 IEC C13 10A per group) |
Output voltage and frequency4, THDU, efficiency5 |
200/208/230/240 /250 V, 50 / 60 Hz autoselect, frequency converter as standard, < 2%, 97% |
Backup time6 |
Eaton MX standard backup time |
10 minutes |
8 minutes |
8 minutes |
8 minutes |
Eaton MX + EXB / MX + 2 EXB / MX + 3 EXB |
45 / 80 / 120 minutes |
35 / 60 / 95 minutes |
35 min (3 EXB)/60 min (6 EXB) /90 min (9 EXB)7 |
35 min (4 EXB)/60 min (8 EXB) /90 min (12 EXB) |
Communications |
Slots |
1 slot (MX) or 2 slots (MX Frame) for Network Management Card, NMC ModBus/JBus card or MC Contacts/Serial card |
Ports |
Remote Power off (RJ11), 5 output contacts (DB9), setup using Solution-Pac8 , (USB and DB9-serial ports), EXB module detection (RJ45), paralleling (DB 15) |
Operating conditions, standards and approvals |
Performance, safety, EMC, surge protection |
IEC/EN 62 040-3, IEC/EN 62 040-1-1, IEC/EN 62 040-2 class A (class B as option), 4 kV IEC 61 643, UL 1778 and CSA 22.29 |
Operating temperature, noise, approvals, guarantee |
0°C to 40°C continuous, 45 dbA10, UL, TüV, GS mark, CB, C-Tick, CE, IEC 61 931, one year11 |
Dimensions H x W x D / Weight |
Eaton MX standard backup tower |
444.5 mm x 130.6 mm x 735 mm / 57 kg |
Tower 690 mm high (795 mm casters) x 444.5 mm wide x 735 mm deep / 250 kg |
Eaton MX standard backup rack |
3U x 444.5 mm wide compatible with 800-1000 mm deep rack |
Rack 16U x 444.5 mm wide, compatible with 800-1000 mm deep rack |
Eaton MX EXB battery unit tower / rack |
444.5 mm x 130.6 mm x 650 mm / 3U x 444.5 mm wide / 70 kg |
Dimensions same as MX Frame / 194 kg for 15 kVA, 239 kg for 20 kVA |
Eaton MX ModularEasy, paralleling kit |
Dimensions same as EXB battery unit / 10 kg |
/ |
Customer Service & Support |
1 year guarantee, including batteries |
Warranty+ |
Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality ) |