Technical Specifications |
700 |
1000 - 1000 RT2U |
1500 - 1500 RT2U |
2200 |
3000 - 3000 XL |
Rating (VA/W) |
700 VA / 630 W |
1000 VA / 900 W1 |
1500 VA / 1350 W1 |
2200 VA / 1980 W |
3000 VA / 2700 W1 |
Format |
Mini tower |
Mini tower or RT2U (tower/rack 2U) |
RT2U (tower / rack 2U) and RT3U (tower / rack 3U) |
Electrical characteristics |
Architecture |
On-line double conversion with automatic by-pass and power factor correction |
Input voltage and frequency ranges without using batteries |
100/120/140/160 V(2) to 284V - 40 to 70 Hz |
100/120/160/184 V(2) to 284V - 40 to 70 Hz |
Output voltage and frequency |
230 V (adjustable to 200/208/220/240/250 V), 50/60 Hz auto-select or frequency converter mode |
230 V (adjustable to 200/208/220/240 V), 50/60 Hz auto-select or frequency converter mode |
Connections |
Input |
1 IEC C14 (10A) socket |
IEC C20 (16A) or terminal block on HotSwap MBP HW (Hard-Wired) |
Outputs |
6 IEC C13 (10A) sockets |
8 IEC C13 (10A) sockets + 1 IEC C19 (16A) socket |
Remotely controlled Powershare sockets |
2 independent groups: 2 + 1 IEC C13 (10A) sockets |
2 groups of 2 x IEC C13 (10A) on Eaton EX |
Additional outputs with HotSwap MBP FR/DIN/BS/IEC/HW |
4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10A sockets or terminal blocks (HW version) |
Additional outputs with FlexPDU FR/DIN/BS/IEC |
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10A sockets |
Battery |
Typical backup times for 50 and 70% load (6) except for Eaton EX 3000 XL5 |
EX |
16 min / 10 min |
18 min / 12 min |
13 min / 9 min |
17 min / 12 min |
15 min / 10 min |
EX + 1 EXB |
/ |
75 min / 50 min |
50 min / 35 min |
85 min / 60 min |
60 min / 40 min |
EX + 4 EXB |
/ |
250 min / 200 min |
180 min / 120 min |
285 min / 200 min |
190 min / 150 min |
Battery management |
Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external battery units => continuous maximisation of backup time + deep discharge protection |
Interfaces |
Indicators and display |
3 LEDS + adjustable multilingual display: display of measurements, access to control and set-up menus |
Communication ports |
1 USB port + 1 RS232 serial port and relay contacts4 + 1 mini terminal block for remote ON/OFF and emergency stop |
Communications card slots |
1 slot for NMC Minislot card (included in Netpack version) or NMC ModBus/JBus or MC Contacts/Serial |
Operating conditions, standards and approvals |
Operating temperature noise level |
0°C to 40°C continuous, 45 dBA |
Performance - Safety - EMC |
IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class |
Approvals |
CE, TüV GS, CB report, cTüV-US |
CE, TüV, CB Report, UL |
Dimensions W x H x D / Weight |
EX |
242 x 153 x 440 mm / 12.5 kg |
242 x 153 x 440 mm / 15 kg |
242 x 153 x 440 mm / 18 kg |
131 x 440 x 490 mm (compatible with 600 mm deep rack) / 30 kg (3000 XL = 18 kg) |
EX RT2U |
/ |
86.5 x 438 x 483 mm / 18 kg |
86.5 x 438 x 483 mm / 20.5 kg |
86 x 440 x 640 mm / 31 kg |
EX EXB |
/ |
242 x 153 x 440 mm / 21 kg |
131 x 440 x 490 mm (compatible with 600 mm deep rack) / 42 kg |
EX EXB RT2U |
/ |
86.5 x 438 x 483 mm / 24.5 kg |
/ |
/ |
Customer Service & Support |
2 years warranty |
Standard product exchange, including the battery |
Warranty+ |
Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality ) |