Technical Specifications |
1250 |
1750 |
2500 |
3000 |
Rating (VA/W) |
1250 VA / 1150 W |
1750 VA / 1600 W |
2500 VA / 2250 W |
3000 VA / 2700 W |
Format |
RT2U (tower / rack 2U) |
RT2U (tower / rack 2U) |
RT2U (tower / rack 2U) |
RT2U & RT3U |
Electrical characteristics |
Technology |
Line-Interactive High Frequency (Booster + Fader) |
Input voltage and frequency ranges without using batteries |
160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system), up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software. |
Output voltage and frequency |
230 V (+6/-10 %) (Adjustable to 200 V (10 % derating of output power) / 208 V / 220 V / 230 V / 240 V), 50/60 Hz +/- 0.1 % |
Connections |
Input |
1 IEC C14 (10 A) socket |
1 IEC C14 (10 A) socket |
1 IEC C20 (16 A) socket |
1 IEC C20 (16 A) socket |
Outputs |
8 IEC C13 (10 A) |
8 IEC C13 (10 A) |
8 IEC C13 (10 A) sockets
1 IEC C19 (16 A) socket |
8 IEC C13 (10 A) sockets
1 IEC C19 (16 A) socket |
Remotely controlled sockets |
2 groups of 2 x IEC C13 (10 A) |
Additional outputs with HS MBP |
4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10 A sockets or terminal blocks (HW version) |
Additional outputs with FlexPDU |
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10 A sockets |
Batteries |
Typical backup times for 50 and 70% load* |
Evolution S |
20/14 mn |
14/9 mn |
17/11 mn |
15/10 mn |
Evolution S + 1 EXB |
105/60 mn |
60/36 mn |
85/55 mn |
60/42 mn |
Evolution S + 4 EXB |
300/200 mn |
180/115 mn |
290/200 mn |
210/135 mn |
Battery management |
Automatic weekly test (period adjustable), automatic recognition of external battery units => continuous maximisation of backup time + deep discharge protection |
Interfaces |
Communication ports |
1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously) + 1 mini terminal block for remote ON/OFF and Remote Power Off |
Communications card slots |
1 slot for NMC Minislot card (included in Netpack versions) or NMC ModBus/JBus or MC Contacts/Serial |
Operating conditions, standards and approvals |
Operating temperature |
0 to 40°C |
Noise Level |
< 45 dBA |
< 45 dBA |
< 50 dBA |
< 50 dBA |
Performance - Safety - EMC |
IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 EN 50091-2 class B (EMC), IEC/EN 62040-3 (Performance), IEC/EN 61000-4-2, 61000-4-3, 61000-4-4; 61000-4-5, 61000-4-6, 61000-4-8 (EMI) |
Approvals |
CE, CB report, TÜV |
Dimensions W x H x D / Weight |
Dimensions |
440 x 509 x 86.2 (2U) mm |
440 x 509 x 86.2 (2U) mm |
440 x 634 x 86.2 (RT2U) mm
440 x 484 x 130.7 (RT3U) mm |
440 x 634 x 86.2 (RT2U) mm
440 x 484 x 130.7 (RT3U) mm |
Weight of the Tower/Rack |
24.3 kg |
26.6 kg |
33.8 kg |
33.8 kg (RT2U) - 34.3 kg (RT3U) |
Dimensions of EXB |
See UPS |
Weight of the EXB |
30.4 kg |
30.4 kg |
41.7 kg |
41.7 kg |
Customer Service & Support |
2 years warranty |
Standard product exchange, including the battery |
Warranty+ |